AWWA C511-17(R21) Reduced-Pressure Principle Backflow Prevention Assembly
American Water Works Association
2029:-
Tillfälligt slut online – klicka på "Bevaka" för att få ett mejl så fort varan går att köpa igen.
This standard describes the reduced-pressure principle backflow prevention assembly for potable water applications. The assembly shall be capable of withstanding a working water pressure of at least 150 psi (1,034 kPa) without damage to working parts or impairment of function and for operation on hot- or cold-water lines. This standard describes hot- and cold-water reduced-pressure principle backflow prevention assemblies. Assemblies shall be designed to operate, at a minimum, at a temperature range of 33F to 140F (1C to 60C). Hot-water assemblies shall be designed to operate, at a minimum, in water at a temperature range of 33F to 180F (1C to 82C). A complete assembly consists of a mechanical, independently operating, hydraulically dependent relief valve located between two independently operating, internally loaded check valves that are located between two tightly closing resilient seated shutoff valves with four properly placed resilient-seated test cocks (see Sec. 4.3.1.3).